6.8.1 General window

1) Min. Hold time

[Min. Hold Time] is for setting the minimum combo time for object, if pressing time is more than setting time, the object will do operation continuously.

Example:

The setting time is 2000 ms;

If users press object less than 2000 ms, the object only does one operation;

If users press object more than 2000 ms, the object will do operation continuously;

Note:

It will conflict with the time interval of the loop pop-up prompt box when the user permissions are insufficient. Therefore, when using this setting, please don't select [Every time] mode in [Security]-[User permission] of object.

2) Indirect Address

Users could read data from dynamic address and write data to dynamic address by [Indirect Address]. The indirect addresses setting window as below picture shows.

Write Address: indirect write address decide to the final write address. And it can support three addresses.

For example:

There is only one address, No.1=HDW210, and the object’s address is HDX200.0. In this situation, HMI will do the following operations:

  • HMI reads value in HDW210, if the HDW210=1;

  • The object’s address change to HDX200.1;

  • So the value will be written to HDX200.1;

Read Address: indirect read address decide to the final read address. Read address up to three.

For example:

There are three indirect addresses for reading, No. 1 is HDW0, No. 2 is HDW10, and No. 3 is HDW20. And the object’s address is HDW100.

In this situation, HMI will do the following operations:

  • HMI reads No. 3 address value firstly, if HDW20=3;

  • The No. 2 address will change to HDW (10+3), and HMI will read the value in HDW13, if HDW13=7;

  • The No.1 address will change to HDW (0+7), and the HMI will read the value in HDW7, if HDW7=6;

  • The object’s address will change to HDW (100+6), and then this object will display the HDW106’s

Last updated