11.2 Allen-Bradley MicroLogix
MicroLogix 1000/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
HMI settings
Item | Settings | Note |
Protocol | Allen-Bradlley MicroLogix | |
Connection | RS232 | |
Baud rate | 19200 | |
Data bit | 8 | |
Parity | None | |
Stop bit | 1 | |
PLC station No. | 1 |
Address list
Type | Device registers | Format | Range | Note |
Bit | I | I d.d | 0.0~255.15 | |
O | O d.d | 0.0~255.15 | ||
B | B nnhh.dd | 0.0~ffff.15 | nn: block number (hex) | |
S | S d.d | 0.0~255.15 | ||
N | N nnhh.dd | 0.0~ffff.15 | nn: block number (hex) | |
Word | S | S d | 0~255 | |
TS | TS nnhh | 0~ffff | nn: block number (hex) | |
TP | TP nnhh | 0~ffff | ||
CS | CS nnhh | 0~ffff | ||
CP | CP nnhh | 0~ffff | ||
N | N nnhh | 0~ffff | ||
C | C nnhh | 0~ffff | ||
T | T nnhh | 0~ffff | ||
R | R nnhh | 0~ffff |