11.14 MODBUS RTU Slave (All function)/(All function OneBaseAddress)
Supported Series: MODBUS RTU CONTROLLER
HMI works as MODBUS MASTER coontecting with SLAVE.
The address in [All function] start from 0, the address in [All function OneBaseAddress] start from 1 (offset 1).
HMI settings
Items | Settings | Note |
Protocol | MODBUS RTU Slave (All function)/( All function OneBaseAddress) | |
Connection | RS485/RS232 | |
Baud rate | 2400~187500 | |
Data bit | 8 | |
Parity | Even/ Odd/ None | |
Stop bit | 1/2 | |
PLC station No. | 0~255 |
Address list
Type | Register | Function code & Description |
Word | ||
3 | 04 (read input register: read current binary value in one or more input registers) 06 (write single register: write a binary value to a holding register) 10 (write values to multiple addresses ) | |
4 | 03 (read holding register: read current binary value in one or more holding registers) 06 (write single register: write a binary value to a holding register) 10 (write values to multiple addresses ) | |
W6 | 03 (read holding register: read current binary value in one or more holding registers) 06 (write single register: write a binary value to a holding register) 10 (write values to multiple addresses ) | |
W16 | 03 (read holding register: read current binary value in one or more holding registers) 10 (write values to multiple addresses ) | |
Bit | ||
0 | 01 (Read coil state) 05 (Force a single coil to force the on/off state of a logic coil) 0F (Write multiple bits, ie write continuously) | |
1 | 02 (Read the input state) 05 (Force a single coil to force the on/off state of a logic coil) 0F (Write multiple bits) | |
W5 | 01 (Read coil state to obtain the current state of a set of logic coils) 05 (Force a single coil to force the on/off state of a logic coil) 0F (Write multiple bits) | |
W15 | 01 (Read coil state to obtain the current state of a set of logic coils) 0F (Write multiple bits) |
✎Note:
Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats. The function codes sent out are the same as those that read and write words.
Station number for more than one slaves
If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
Cable wiring
1) RS485
2) RS232
✎Note:
COM3 is available in PI8000 series and advanced series;
Last updated