11.21 SHIMADEN Standard protocol

Supported series: SHIMADEN MR13 series

HMI setting

Items

Settings

Note

Protocol

SHIMADEN standard protocol

Connection

RS485 (1200, 1, 7, EVEN)

Port No.

None

PLC station No.

0

Address list

Device address

HMI register

Address range

Type

0100-010B(HEX)

MR100

100256-300267

Read only

0111-0126(HEX)

MR111

100273-300294

Read only

0184-0192(HEX)

MR184

100388-300402

Write only

0280-0282(HEX)

MR280

100640-300642

Read only

0300-030B(HEX)

MR300

100768-300779

Read/write

0314-0317(HEX)

MR314

100788-300791

Read/write

031A(HEX)

MR31A

100794-300794

Read/write

0320-0321(HEX)

MR320

100800-300801

Read/write

0400-0504(HEX)

MR400

101024-301284

Read/write

0506(HEX)

MR506

101286-301286

Read/write

0510-0514(HEX)

MR510

101296-301300

Read/write

0516-0524(HEX)

MR516

101302-301316

Read/write

0526(HEX)

MR526

101318-301318

Read/write

0580-08C3(HEX)

MR580

101408-302243

Read/write

--

Ctrl

0-2

--

Note:

1) The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);

2) The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;

3) The Ctrl register is used to store the control group number and BCC check mode.

Ctrl register description

1) The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.

2) Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .

3) Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;

4) Ctrl3 reserved

Note:

After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.

Cable wiring

Note:

COM3 is available in PI8000 series and advanced series