11.26 Siemens S7-XXX Ethernet
Supported Series: Siemens S7-1200 and S7-1500
HMI Setting
Items | Settings | Note |
Protocol | Siemens S7-XXX | |
Connection | Ethernet | |
Port No. | 102 | |
PLC station No. | 1 (for S7-1500)/ 2 (for S7-1200) |
Address list
Type | Device register | HMI register | Format | Range | Note |
Bit | |||||
I | I | M d.o | d:0--9999 o:0-7 | ||
Q | Q | Q d.o | d:0--9999 o:0-7 | ||
M | M | M d.o | d:0--9999 o:0-7 | ||
DB0.DB-DB99.DB | DBxDB | DBxDB nndddd.o | nn:0-9999, dddd:0-9999, o:0-7 | nn: DB No. dddd: address value o: digit address | |
Word | |||||
M | MB | MB d | d:0-99999 | ||
M | MW | MW d | d:0-99999 | MW0=MB(0~1) MW2=MB(2~3) Address value is a multiple of 2 | |
M | MD | MD d | d:0-99999 | MD0=MB(0~3) MD4=MB(4~7) Address value is a multiple of 4 | |
I | IW | IW d | d:0-99999 | ||
Q | QW | QW d | d:0-99999 | ||
DB0.DB-DB99.DB | DBxDBB | DBxDBB nndddd | nn: 0-9999 dddd:0-9999 | nn: DB No. dddd: address value | |
DB0.DB-DB99.DB | DBxDBW | DBxDBW nndddd | nn:0-9999 dddd:0-9999 | nn: DB No. dddd: address value Address value is a multiple of 2 | |
DB0.DB-DB99.DB | DBxDBD | DBxDBD nndddd | nn:0-9999 dddd:0-9999 | nn: DB No. dddd: address value Address value is a multiple of 4 |
Communication settings
13) Enable HMI Ethernet in [Project Settings];
14) Set PLC IP in [Device IP] settings;
✎Note:
3) The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
4) HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.