12.2 System special address (HSW/HSX)

12.2.1 System data addresses

Address

Function

Description

HSW0

Language switch

Multiple language could be set in the project, HMI support maximum 8 languages.

HSW1

Beep frequency

Frequency range (0-4999)

HSW2

Beep volume

Volume range (0-80)

HSW3

Beep time

Unit: ms

HSW4

Beep switch

=0: Turn ON;

=1: Turn OFF;

HSW5

Alarm lamp

=0: No alarm;

=1: Alarm;

HSW6~7

The number of alarms

The number of alarm (it including released and not released)

HSW8

Number of not released alarms

The number of not released alarms

HSW9

Time out tip message

=0: Visible

=1: Invisible

HSW10

System language

=0: Chinses;

=1: English;

HSW12

Screen swicth

= 0: Only HSW control the screen switch

= 1: Only HUW control the screen switch

HSW13

Designated screen switch

The screen will switch to designated screen

HSW24

Reboot HMI

=1: Reboot

HSW28

Local time: year

Range: 0~9999

HSW29

Local time: month

Range: 1~12

HSW30

Local time: day

Range: 1~31

HSW31

Local time: hour

Range: 0~23

HSW32

Local time: minute

Range: 0~59

HSW33

Local time: second

Range: 0~59

HSW34

Local time: week

On simulator:

=0: Sunday;

=1: Monday;

=2: Tuesday;

=3: Wednesday;

=4: Thursday;

=5: Friday;

=6: Saturday;

On HMI:

=0: Sunday;

=1: Saturday;

=2: Monday;

=3: Tuesday;

=4: Wednesday;

=5: Thursday;

=6: Friday,

HSW134

Script reading

=0: Read from HMI cache

=1: Read from PLC

HSW135

Confirm installment password

Confirm button for installment password

HSW151

Installment due

Number of days to installment due

HSW185~200

Installment password

Enter installment password

HSW242

Prompt result of recipe operation

=1: Download, start

=3: Download, files don’t exist

=4: Download, members don’t exist

=5: Download, groups don’t exist

=6: Download, success

=7: Upload, start

=8: Upload, execute error

=9: Upload, files don’t exist

=10: Upload, members don’t exist

=11: Upload, groups don’t exist

=12: Upload, success

=13: Insert, start

=14: Insert, execute error

=15: Insert, files don’t exist

=16: Insert, members don’t exist

=17: Insert, groups don’t exist

=18: Insert, success

=19: Delete, start

=20: Delete, execute error

=21: Delete, files don’t exist

=22: Delete, members don’t exist

=23: Delete, groups don’t exist

=24: Delete, success

=25: Delete and sort, start

=26: Delete and sort, execute error

=27: Delete and sort, files don't exist

=28: Delete and sort, members don't exist

=29: Delete and sort, groups don't exist

=30: Delete and sort, success

HSW243

Prompt result of recipe index

=31: Recipe index, start

=32: Recipe index, execute error

=33: Recipe index, files don’t exist

=34: Recipe index, members don’t exist

=35: Recipe index, groups don’t exist

=36: Recipe index, success

HSW521

Delete graph and alarm record

=0: No operation

=1: HSX521.0 = 1, delete all records;

=2: HSX521.1 = 1, delete all trend graph;

=4: HSX521.2 = 1, delete all alarms;

=16: HSX521.4 = 1, delete history XY plot;

=32: HSX521.5 = 1, delete data records in SD card or flash dish;(Please make a setting which is saved to flash disk or SD card in project setting);

=64: HSX521.6 = 1, delete alarms records in SD card or flash dish; (Please make a setting which is saved to flash disk or SD card in project setting).

HSW522

Copy and paste the alarm/data files in flash to the USB flash disk

=0: No operation

=1: HSX522.0 = 1, copy all record

=2: HSX522.2 = 1, copy history XY trend graph

=8: HSX522.3 = 1, copy alarm record

=32: HSX522.5 = 1, copy recipe

HSW523

Copy and paste the alarm/data files in flash to the SD card

=0: No operation

=1: HSX523.0 = 1, copy all record

=4: HSX523.2 = 1, copy history XY trend graph

=8: HSX523.3 = 1, copy alarm record

HSW524

Copy and paste the alarm/data files in SD card to the USB flash disk

=0: no operation

=4: HSX524.2 = 1, copy history XY trend graph

=8: HSX524.3 = 1, copy alarm record

=16: HSX524.4 = 1, copy history alarm record

=32: HSX524.5 = 1, copy data record

HSW525

Copy and paste the alarm/data files in USB flash disk to SD card

=0: no operation

=4: HSX525.2=1, copy history XY trend graph

=8: HSX525.3 = 1, copy alarm record

=16: HSX525.4=1, copy history alarm record

=32: HSX525.5= 1, copy data record

HSW526

Delete file list

=0: no operation

=1: HSX526.0 = 1, delete designated file

=2: HSX526.1 = 1, delete all files

HSW527

Eject USB flash disk/SD card

=0: No operation

=1: Eject USB flash disk

=2: Eject SD card

HSW528

The state of USB flash disk

=1: USB flash disk is detected

=2: Ejecting USB flash disk, please waiting…

=3: USB flash disk ejected

HSW529

The state of SD card

=1:SD card is detected

=2: Ejecting SD card, please waiting…

=3: SD card ejected

HSW550~849

Communication control

For communication control and communication lamp (please refer to communication control sector for detailed)

HSW850

Network state

Display network state

=0: Disconnected;

=1: only connected LAN, so APP can’t access HMI;

=2: Connected WECON Cloud, APP and web could access HMI;

HSW855

Backlight Control

HSX855.0 = 1: turn on the backlight and reset automatically after being triggered;

HSX855.1= 1: turn off the backlight and reset automatically after being triggered;

HSW856

Close the sub-screen or indirect screen when switching screen control (when the former screen is switched to the current screen)

=0: close the sub-screen, including the indirect screen;

=1: not to close.

HSW857

Permission in remote access (web page, mobile APP, cloud platform, etc.)

=0: users could switch the screen, control the switch and update data in remote access;

=1: users could only control function switch, i.e., could only switch the screen, view data and switch state, but could not operate or update them.

HSW881

Storage of Record files

It is used for controlling saving alarm/data record files to U disk / SD card.

= 0: Save to storage;

= 1: Don't save to storage;

HSW882

Storage device status

HDX882.0=0 USB flash doesn’t execute storage or storage finished;

HDX882.0=1 USB flash is reading data, don’t remove USB flash;

HDX882.1=0 SD card doesn’t execute storage or storage finished;

HDX882.1=1 SD card is reading data, don’t remove SD card;

HSW884

Into setup screen

= 0: Do not into setup screen

= 1: Into setup screen

HSW885

When the control object hides the address read failure (communication failure), set the display mode of the object

= 0: displayed by object setting.

=1: control address read failure, the address control of all objects is hidden, not displayed.

=2: control address read failure, the address control of all objects is displayed, not hidden.

HSW893

User Restriction Control Address like the special address HUW1000 feature, refer to "User Rights "

=1: User Log in

=2: Change User password

=3: User Log out

=4: New user

=5: Delete user

=6: Add user rights

=8: Add Hide features

=9: Delete Profile

=10: Export Profile

=11: Import profile

=12: Export log file

=13: Delete log file

HSW900

Quick update frequency settings for objects

Valid when the object is enabled for [quick update]. Default: 5.

Range: 1 (fastest) ~ 50 (slowest)

HSW920

Maximum periods (Static mode)

Numeric Input/ Display (range: 0-12)

HSW921 ~ 924

Admin key (Static mode)

Character Input/ Display (length: 8)

HSW925 ~ 928

1st period key (Static mode)

Character Input/ Display (length: 8)

HSW929 ~ 933

1st expiry time (Static mode)

Numeric Input/ Display (YYYYMMDDHHMM)

HSW935 ~ 938

2nd period key (Static mode)

Character Input/ Display (length: 8)

HSW939 ~ 943

2nd expiry time (Static mode)

Numeric Input/ Display (YYYYMMDDHHMM)

HSW945 ~ 948

3rd period key (Static mode)

Character Input/ Display (length: 8)

HSW949 ~ 953

3rd expiry time (Static mode)

Numeric Input/ Display (YYYYMMDDHHMM)

HSW955 ~ 958

4th period key (Static mode)

Character Input/ Display (length: 8)

HSW959 ~ 963

4th expiry time (Static mode)

Numeric Input/ Display (YYYYMMDDHHMM)

HSW965 ~ 968

5th period key (Static mode)

Character Input/ Display (length: 8)

HSW969 ~ 973

5th expiry time (Static mode)

Numeric Input/ Display (YYYYMMDDHHMM)

HSW975 ~ 978

6th period key (Static mode)

Character Input/ Display (length: 8)

HSW979 ~ 983

6th expiry time (Static mode)

Numeric Input/ Display (YYYYMMDDHHMM)

HSW985 ~ 988

7th period key (Static mode)

Character Input/ Display (length: 8)

HSW989 ~ 993

7th expiry time (Static mode)

Numeric Input/ Display (YYYYMMDDHHMM)

HSW995 ~ 998

8th period key (Static mode)

Character Input/ Display (length: 8)

HSW999 ~ 1003

8th expiry time (Static mode)

Numeric Input/ Display (YYYYMMDDHHMM)

HSW1005 ~1008

9th period key (Static mode)

Character Input/ Display (length: 8)

HSW1009 ~ 1013

9th expiry time (Static mode)

Numeric Input/ Display (YYYYMMDDHHMM)

HSW1015 ~1018

10th period key (Static mode)

Character Input/ Display (length: 8)

HSW1019 ~ 1023

10th expiry time (Static mode)

Numeric Input/ Display (YYYYMMDDHHMM)

HSW1025 ~1028

11th period key (Static mode)

Character Input/ Display (length: 8)

HSW1029 ~ 1033

11th expiry time (Static mode)

Numeric Input/ Display (YYYYMMDDHHMM)

HSW1035 ~1038

12th period key (Static mode)

Character Input/ Display (length: 8)

HSW1039 ~ 1043

12th expiry time (Static mode)

Numeric Input/ Display (YYYYMMDDHHMM)

HSW1046

Current period (Static mode)

Current period (Range 1-13)

HSW1047

Save settings (Static mode)

HSX1047.0=1: Save static installment information

HSX1047.1=1: Write installment information to registers

HSW1070

The time interval (seconds) since the last time the screen was clicked

Shows how long the current screen has not been clicked, using a decimal unsigned double word (Numeric Input/ Display).

Note: This register is cleared to zero regardless of which user clicks on the screen.

HSW1086

Address mapping polling cycle, unit: ms

Address mapping polling cycle, effective range: 40~1000ms, default: 300ms.

HSW1087

Write interval in address mapping

Address length setting, triggers a write operation when N addresses change. The effective range: 0-5, and default is 2. When N more than 5, it becomes 5.

HSW1088

Write interval in scripts

Address length setting, triggers a write operation when N addresses change. The effective range: 0-5, and default is 2. When N more than 5, it becomes 5.

HSW1089

Interval in read through

Address length setting, triggers a write operation when N addresses change. The effective range: 0-5, and default is 2. When N more than 5, it becomes 5.

HSW1140

Trigger objects security function

=0, Disable

=1, Enable

HSW1141

Each level independent

=0, No, high-level passwords can unlock low-level

=1, Yes, high-level passwords cannot unlock low-level

HSW1142

Initialization level

Initialization level while HMI running

HSW1144

Password for Level 1

Maximum character length 8 allowed in password (numbers, letters (case sensitive)).

HSW1148

Password for Level 2

Maximum character length 8 allowed in password (numbers, letters (case sensitive)).

HSW1152

Password for Level 3

Maximum character length 8 allowed in password (numbers, letters (case sensitive)).

HSW1156

Password for Level 4

Maximum character length 8 allowed in password (numbers, letters (case sensitive)).

HSW1160

Password for Level 5

Maximum character length 8 allowed in password (numbers, letters (case sensitive)).

HSW1164

Password for Level 6

Maximum character length 8 allowed in password (numbers, letters (case sensitive)).

HSW1168

Password for Level 7

Maximum character length 8 allowed in password (numbers, letters (case sensitive)).

HSW1172

Password for Level 8

Maximum character length 8 allowed in password (numbers, letters (case sensitive)).

HSW1176

Password for Level 9

Maximum character length 8 allowed in password (numbers, letters (case sensitive)).

HSW1180

Password for Level 10

Maximum character length 8 allowed in password (numbers, letters (case sensitive)).

HSW1184

Password for Level 11

Maximum character length 8 allowed in password (numbers, letters (case sensitive)).

HSW1188

Password for Level 12

Maximum character length 8 allowed in password (numbers, letters (case sensitive)).

HSW1192

Save and undo settings

=1, Save, save the data of HSW1140, HSW1141, HSW1142, HSW1144-HSW1188 to a file, the data will not change after restart (note: the file will be deleted if download a new project)

=2,Undo, undo modification of HSW1140、HSW1141、HSW1142、HSW1144-HSW1188 (note: If click save, the operation is invalid)

HSW10000~19999

Power OFF protection

HSW10035

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local IP address high endian 1

HSW10036

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local IP address high endian 2

HSW10037

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local IP address high endian 3

HSW10038

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local IP address high endian 4

HSW10039

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local mask IP address high endian 1

HSW10040

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local mask IP address high endian 2

HSW10041

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local mask IP address high endian 3

HSW10042

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local mask IP address high endian 4

HSW10043

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local gateway high endian 1

HSW10044

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local gateway high endian 2

HSW10045

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local gateway high endian 3

HSW10046

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local gateway high endian 4

HSW10047

The Ethernet parameter is only editable, when the settings are programmed in HMI software.

Local port address

HSW10048

Displays the MAC code of the current network card

(Hexadecimal display)

Local MAC code high word 1

HSW10049

Displays the MAC code of the current network card

(Hexadecimal display)

Local MAC code high word 2

HSW10050

Displays the MAC code of the current network card

(Hexadecimal display)

Local MAC code high word 3

HSW10051

Displays the MAC code of the current network card

(Hexadecimal display)

Local MAC code high word 4

HSW10052

Displays the MAC code of the current network card

(Hexadecimal display)

Local MAC code high word 5

HSW10053

Displays the MAC code of the current network card

(Hexadecimal display)

Local MAC code high word 6

HSW10461~10493

Remote access password

8-character remote access password

HSW10494~10558

Machine ID (Read only)

Machine ID for remote access (read only 64-bit)

HSW10576

Save dynamic installment settings

HSX10576.0=1: save settings

HSW10577

Control address for installment

HSX10577.0=0: disable dynamic installment

HSX10577.0=1: enable dynamic installment

HSX10577.1=0: disable static installment

HSX10577.1=1: enable static installment

HSW10578-10583

Character Input/ Display (length: 6)

Password

HSW10584-10586

Numeric Input/ Display (YYYYMMDD)

Expiry time

HSW10587-10589

Numeric Input/ Display (YYYYMMDD)

Expiry time (set in program)

HSW10590

Background light time

Set the light time for background

=0: lit all the time;

Others: light time (unit: S)

HSW10591

Backlight brightness adjustment

Backlight brightness range: 1 (darkest) ~ 100 (brightest)

HSW10603

Set the printer to print orientation

Set the print direction:

=1: Forward printing

=2: Reverse print

Other: Forward print

HSW10604

Print dot type

=1: 8 dot matrix type;

=2: 24 dot matrix type;

Other: 8 dot matrix type

HSW10605

Printer print width

Set the width of the printer to print (in pixels), such as HSW10605 = 394: The printer supports images with a print width of 394 pixels

HSW10606

Printer instruction type

=1: Graphic print type

=2: Dot density printing type

HSW10607

Cut function

=1: Enable the cut function

=2: Disable cutting function

HSW10608

Print the alignment of the text

=1: Left justified

=2: Center alignment

=3: Right justified

12.2.2 Serial port communication configuration

Port

Address

Function

Description

COM1

HSW010061

Communication

=0: RS232

=1: RS485

=2: RS422

HSW010062

Baud rate

=0: 1200

=1: 2400

=2: 4800

=3: 9600

=4: 19200

=5: 38400

=6: 57600

=7: 115200

=8: 230400

HSW010063

Data bit

=7: 7 bit

=8: 8 bit

HSW010064

Stop bit

=1: 1 bit

=2: 2 bit

HSW010065

Check bit

=0: None

=1: ODD

=2: EVEN

HSW010066

Wait timeout

HSW010067

Read timeout

HSW010068

Retry time

HSW010069

Retry timeout

HSW010070

HMI station number

HSW010071

PLC station number

COM2

HSW010072

Communication

=0: RS232

=1: RS485

HSW010073

Baud rate

=0: 1200

=1: 2400

=2: 4800

=3: 9600

=4: 19200

=5: 38400

=6: 57600

=7: 115200

=8: 230400

HSW010074

Data bit

=7: 7 bit

=8: 8 bit

HSW010075

Stop bit

=1: 1 bit

=2: 2 bit

HSW010076

Check bit

=0: None

=1: ODD

=2: EVEN

HSW010077

Wait timeout

HSW010078

Read timeout

HSW010079

Retry time

HSW010080

Retry timeout

HSW010081

HMI station number

HSW010082

PLC station number

COM3

HSW010083

Communication

=0: RS232

=1: RS485

=2: RS422

HSW010084

Baud rate

=0: 1200

=1: 2400

=2: 4800

=3: 9600

=4: 19200

=5: 38400

=6: 57600

=7: 115200

=8: 230400

HSW010085

Data bit

=7: 7 bit

=8: 8 bit

HSW010086

Stop bit

=1: 1 bit

=2: 2 bit

HSW010087

Check bit

=0: None

=1: ODD

=2: EVEN

HSW010088

Wait timeout

HSW010089

Read timeout

HSW010090

Retry time

HSW010091

Retry timeout

HSW010092

HMI station number

HSW010093

PLC station number

COM1-2

HSW010094

Communication

=0: RS232

=1: RS485

=2: RS422

HSW010095

Baud rate

=0: 1200

=1: 2400

=2: 4800

=3: 9600

=4: 19200

=5: 38400

=6: 57600

=7: 115200

=8: 230400

HSW010096

Data bit

=7: 7 bit

=8: 8 bit

HSW010097

Stop bit

=1: 1 bit

=2: 2 bit

HSW010098

Check bit

=0: None

=1: ODD

=2: EVEN

HSW010099

Wait timeout

HSW010100

Read timeout

HSW010101

Retry time

HSW010102

Retry timeout

HSW010103

HMI station number

HSW010104

PLC station number

COM2-2

HSW010105

Communication

=0: RS232

=1: RS485

=2: RS422

HSW010106

Baud rate

=0: 1200

=1: 2400

=2: 4800

=3: 9600

=4: 19200

=5: 38400

=6: 57600

=7: 115200

=8: 230400

HSW010107

Data bit

=7: 7 bit

=8: 8 bit

HSW010108

Stop bit

=1: 1 bit

=2: 2 bit

HSW010109

Check bit

=0: None

=1: ODD

=2: EVEN

HSW010110

Wait timeout

HSW010111

Read timeout

HSW010112

Retry time

HSW010113

Retry timeout

HSW010114

HMI station number

HSW010115

PLC station number

12.2.3 Ethernet communication configuration

No.

Address

Function

Description

1

HSW11004

Ethernet parameter configuration for communication number 1 in list. Configure those addresses according to connected device. After configuration, wait for 5 seconds and restart the HMI.

IP address high endian 1

HSW11005

IP address high endian 2

HSW11006

IP address high endian 3

HSW11007

IP address high endian 4

HSW11008

Port number

HSW11009

=2 TCP; =3 UDP

HSW11010

Reserved

2

HSW11011

Ethernet parameter configuration for communication number 2 in list. Configure those addresses according to connected device. After configuration, wait for 5 seconds and restart the HMI.

IP address high endian 1

HSW11012

IP address high endian 2

HSW11013

IP address high endian 3

HSW11014

IP address high endian 4

HSW11015

Port number

HSW11016

=2 TCP; =3 UDP

HSW11017

Reserved

32

HSW11221

Ethernet parameter configuration for communication number 32 in list. Configure those addresses according to connected device. After configuration, wait for 5 seconds and restart the HMI.

IP address high endian 1

HSW11222

IP address high endian 2

HSW11223

IP address high endian 3

HSW11224

IP address high endian 4

HSW11225

Port number

HSW11226

=2 TCP; =3 UDP

HSW11227

Reserved

12.2.4 Communication control

Default setting, ON=0; OFF=1. normal=0; error=1

No.

Station No.

Control bit

Communication lamp

1

0~15

HSX550.0~550.15

HSX558.0~558.15

16~31

HSX551.0~551.15

HSX559.0~559.15

32~47

HSX552.0~552.15

HSX560.0~560.15

48~63

HSX553.0~553.15

HSX561.0~561.15

2

0~15

HSX566.0~566.15

HSX574.0~574.15

16~31

HSX567.0~567.15

HSX575.0~575.15

32~47

HSX568.0~568.15

HSX576.0~576.15

48~63

HSX569.0~569.15

HSX577.0~577.15

3

0~15

HSX582.0~582.15

HSX590.0~590.15

16~31

HSX583.0~583.15

HSX591.0~591.15

32~47

HSX584.0~584.15

HSX592.0~592.15

48~63

HSX585.0~585.15

HSX593.0~593.15

4

0~15

HSX598.0~598.15

HSX606.0~606.15

16~31

HSX599.0~599.15

HSX607.0~607.15

32~47

HSX600.0~600.15

HSX608.0~608.15

48~63

HSX601.0~601.15

HSX609.0~609.15

5

0~15

HSX614.0~614.15

HSX622.0~622.15

16~31

HSX615.0~615.15

HSX623.0~623.15

32~47

HSX616.0~616.15

HSX624.0~624.15

48~63

HSX617.0~617.15

HSX625.0~625.15

6

0~15

HSX630.0~630.15

HSX638.0~638.15

16~31

HSX631.0~631.15

HSX639.0~639.15

32~47

HSX632.0~632.15

HSX640.0~640.15

48~63

HSX633.0~633.15

HSX641.0~641.15

7

0~15

HSX646.0~646.15

HSX654.0~654.15

16~31

HSX647.0~647.15

HSX655.0~655.15

32~47

HSX648.0~648.15

HSX656.0~656.15

48~63

HSX649.0~649.15

HSX657.0~657.15

8

0~15

HSX662.0~662.15

HSX670.0~670.15

16~31

HSX663.0~663.15

HSX671.0~671.15

32~47

HSX664.0~664.15

HSX672.0~672.15

48~63

HSX665.0~665.15

HSX673.0~673.15

9

0~15

HSX678.0~678.15

HSX686.0~686.15

16~31

HSX679.0~679.15

HSX687.0~687.15

32~47

HSX680.0~680.15

HSX688.0~688.15

48~63

HSX681.0~681.15

HSX689.0~689.15

10

0~15

HSX694.0~694.15

HSX702.0~702.15

16~31

HSX695.0~695.15

HSX703.0~703.15

32~47

HSX696.0~696.15

HSX704.0~704.15

48~63

HSX697.0~697.15

HSX705.0~705.15

11

0~15

HSX710.0~710.15

HSX718.0~718.15

16~31

HSX711.0~711.15

HSX719.0~719.15

32~47

HSX712.0~712.15

HSX720.0~720.15

48~63

HSX713.0~713.15

HSX721.0~721.15

12

0~15

HSX726.0~726.15

HSX734.0~734.15

16~31

HSX727.0~727.15

HSX735.0~735.15

32~47

HSX728.0~728.15

HSX736.0~736.15

48~63

HSX729.0~729.15

HSX737.0~737.15

13

0~15

HSX742.0~742.15

HSX750.0~750.15

16~31

HSX743.0~743.15

HSX751.0~751.15

32~47

HSX744.0~744.15

HSX752.0~752.15

48~63

HSX745.0~745.15

HSX753.0~753.15

14

0~15

HSX758.0~758.15

HSX766.0~766.15

16~31

HSX759.0~759.15

HSX767.0~767.15

32~47

HSX760.0~760.15

HSX768.0~768.15

48~63

HSX761.0~761.15

HSX769.0~769.15

15

0~15

HSX774.0~774.15

HSX782.0~782.15

16~31

HSX775.0~775.15

HSX783.0~783.15

32~47

HSX776.0~776.15

HSX784.0~784.15

48~63

HSX777.0~777.15

HSX785.0~785.15

16

0~15

HSX790.0~790.15

HSX798.0~798.15

16~31

HSX791.0~791.15

HSX799.0~799.15

32~47

HSX792.0~792.15

HSX800.0~800.15

48~63

HSX793.0~793.15

HSX801.0~801.15