11.15 MODBUS TCP Slave (All function)
Supported series: MODBUS TCP controller
HMI works as MODBUS TCP MASTER coonecting with TCP SLAVE
HMI Setting
Items
Settings
Note
Protocol
MODBUS TCP Slave (All function)
Connection
Ethernet
Port No.
502
PLC station No.
1
Address list
Type
Register
Function code & Description
Word
3
04 (read input register: read current binary value in one or more input registers)
06 (write single register: write a binary value to a holding register)
10 (write values to multiple addresses )
4
03 (read holding register: read current binary value in one or more holding registers)
06 (write single register: write a binary value to a holding register)
10 (write values to multiple addresses )
W6
03 (read holding register: read current binary value in one or more holding registers)
06 (write single register: write a binary value to a holding register)
10 (write values to multiple addresses )
W16
03 (read holding register: read current binary value in one or more holding registers)
10 (write values to multiple addresses )
Bit
0
01 (Read coil state)
05 (Force a single coil to force the on/off state of a logic coil)
0F (Write multiple bits, ie write continuously)
1
02 (Read the input state)
05 (Force a single coil to force the on/off state of a logic coil)
0F (Write multiple bits)
W5
01 (Read coil state to obtain the current state of a set of logic coils)
05 (Force a single coil to force the on/off state of a logic coil)
0F (Write multiple bits)
W15
01 (Read coil state to obtain the current state of a set of logic coils)
0F (Write multiple bits)
Communication settings
1) Enable HMI Ethernet in [Project Settings];
2) Set PLC IP in [Device IP] settings;
Communication cable
Last updated
Was this helpful?