11.15 MODBUS TCP Slave (All function)
Supported series: MODBUS TCP controller
HMI works as MODBUS TCP MASTER coonecting with TCP SLAVE
HMI Setting
Items | Settings | Note |
Protocol | MODBUS TCP Slave (All function) | |
Connection | Ethernet | |
Port No. | 502 | |
PLC station No. | 1 |
Address list
Type | Register | Function code & Description |
Word | ||
3 | 04 (read input register: read current binary value in one or more input registers) 06 (write single register: write a binary value to a holding register) 10 (write values to multiple addresses ) | |
4 | 03 (read holding register: read current binary value in one or more holding registers) 06 (write single register: write a binary value to a holding register) 10 (write values to multiple addresses ) | |
W6 | 03 (read holding register: read current binary value in one or more holding registers) 06 (write single register: write a binary value to a holding register) 10 (write values to multiple addresses ) | |
W16 | 03 (read holding register: read current binary value in one or more holding registers) 10 (write values to multiple addresses ) | |
Bit | ||
0 | 01 (Read coil state) 05 (Force a single coil to force the on/off state of a logic coil) 0F (Write multiple bits, ie write continuously) | |
1 | 02 (Read the input state) 05 (Force a single coil to force the on/off state of a logic coil) 0F (Write multiple bits) | |
W5 | 01 (Read coil state to obtain the current state of a set of logic coils) 05 (Force a single coil to force the on/off state of a logic coil) 0F (Write multiple bits) | |
W15 | 01 (Read coil state to obtain the current state of a set of logic coils) 0F (Write multiple bits) |
Communication settings
1) Enable HMI Ethernet in [Project Settings];
2) Set PLC IP in [Device IP] settings;
Communication cable
Last updated