11.22 Siemens S7-200 Smart (Ethernet)
Supported Series: Siemens S7-200 SMART Series Ethernet Module.
Website: http://www.siemens.com/entry/cc/en/
HMI Setting
Items | Settings | Note |
Protocol | Simens S7-200 Smart Ethernet | |
Connection | Ethernet | |
Port No. | 102 | |
PLC station No. | 2 |
Address list
Type | Device register | HMI register | Format | Range | Note |
Bit | |||||
I | I | I ddddd.o | 0.0~99999.7 | ||
Q | Q | Q ddddd.o | 0.0~99999.7 | ||
V | VWbit | VWbit ddddd.o | 0.0~99999.7 | ||
V | V | V ddddd.o | 0.0~99999.7 | ||
M | M | M ddddd.o | 0.0~99999.7 | ||
SM | SM | ddddd.o | 0.0~99999.7 | ||
S | S | ddddd.o | 0.0~99999.7 | Read only | |
T | T | ddddd | 0~99999 | Timer state, read only | |
C | C | ddddd | 0~99999 | Counter state, read only | |
Word | |||||
I | IW | IW ddddd | 0~99999 | ||
Q | QW | QW ddddd | 0~99999 | ||
AI | AIW | AIW ddddd | 0~99999 | ||
AQ | VB | VB ddddd | 0~99999 | ||
V | VW | VW ddddd | 0~99998 | VW0=VB (0~1) VW2=VB (2~3) Address value is a multiple of 2 | |
V | VD | VD ddddd | 0~99998 | VD0=VB (0~3) VD2=VB (4~7) Address value is a multiple of 4 | |
M | MB | MB ddddd | 0~99999 | ||
M | MW | MW ddddd | 0~99999 | MW0=MB(0~1) MW2=MB(2~3) Address value is a multiple of 2 | |
M | MD | MD ddddd | 0~99999 | MD0=MB(0~3) MD4=MB(4~7) Address value is a multiple of 4 | |
T | TW | TW ddddd | 0~99999 | Value of timer | |
C | CW | CW ddddd | 0~99999 | Value of counter | |
W | SW | SW ddddd | 0~99999 |
Communication settings
7) Enable HMI Ethernet in [Project Settings];
8) Set PLC IP in [Device IP] settings;
PLC IP Address: PLC IP
PLC pot No.: 102(fixed)
Network: TCP_Client_2N (fixed)
Wait timeout: depend on actual network situation (more than 1500 ms)
Communication cable