Supported Series: Siemens S7-200 SMART Series Ethernet Module.
Website:
HMI Setting
Address list
Communication settings
7) Enable HMI Ethernet in [Project Settings];
8) Set PLC IP in [Device IP] settings;
PLC IP Address: PLC IP
PLC pot No.: 102(fixed)
Network: TCP_Client_2N (fixed)
Wait timeout: depend on actual network situation (more than 1500 ms)
Communication cable
Items
Settings
Note
Protocol
Simens S7-200 Smart Ethernet
Connection
Ethernet
Port No.
102
PLC station No.
2
Type
Device register
HMI register
Format
Range
Note
Bit
I
I
I ddddd.o
0.0~99999.7
Q
Q
Q ddddd.o
0.0~99999.7
V
VWbit
VWbit ddddd.o
0.0~99999.7
V
V
V ddddd.o
0.0~99999.7
M
M
M ddddd.o
0.0~99999.7
SM
SM
ddddd.o
0.0~99999.7
S
S
ddddd.o
0.0~99999.7
Read only
T
T
ddddd
0~99999
Timer state, read only
C
C
ddddd
0~99999
Counter state, read only
Word
I
IW
IW ddddd
0~99999
Q
QW
QW ddddd
0~99999
AI
AIW
AIW ddddd
0~99999
AQ
VB
VB ddddd
0~99999
V
VW
VW ddddd
0~99998
VW0=VB (0~1)
VW2=VB (2~3)
Address value is a multiple of 2
V
VD
VD ddddd
0~99998
VD0=VB (0~3)
VD2=VB (4~7)
Address value is a multiple of 4
M
MB
MB ddddd
0~99999
M
MW
MW ddddd
0~99999
MW0=MB(0~1)
MW2=MB(2~3)
Address value is a multiple of 2
M
MD
MD ddddd
0~99999
MD0=MB(0~3)
MD4=MB(4~7)
Address value is a multiple of 4
T
TW
TW ddddd
0~99999
Value of timer
C
CW
CW ddddd
0~99999
Value of counter
W
SW
SW ddddd
0~99999