11.23 Siemens S7-300
Supported Series: Siemens S7-300 series PLC
HMI Setting
Items | Settings | Note |
Protocol | Siemens S7-300 Ethernet | |
Connection | Ethernet | |
Port No. | 102 | |
PLC station No. | 2 | Need to be same as the PLC setting |
Address list
Type | Device register | HMI register | Format | Range | Note |
Bit | |||||
I | I | I ddddd.o | 0.0~99999.7 | ||
Q | Q | Q ddddd.o | 0.0~99999.7 | ||
M | M | M ddddd.o | 0.0~99999.7 | ||
DB0.DB~DB99.DB | DBxDBD | DBxDB nndddd.o | 0.0~99999999.7 | nn: block number; dddd: address; | |
Word | |||||
I | IW | IW ddddd | 0~99999 | ||
Q | QW | QW ddddd | 0~99999 | ||
M | MB | MB ddddd | 0~99999 | ||
MW | MW ddddd | 0~99999 | MW0=MB(0~1) MW2=MB(2~3) Address value is a multiple of 2 | ||
MD | MD ddddd | 0~99999 | MD0=MB(0~3) MD4=MB(4~7) Address value is a multiple of 4 | ||
DB0.DB~DB99.DB | DBxDBB | DBxDBB nndddd | 0~99999999 | nn: block number; dddd: address | |
DBxDBW | DBxDBW nndddd | 0~99999999 | |||
DBxDBD | DBxDBD nndddd | 0~99999999 |
Communication settings
9) Enable HMI Ethernet in [Project Settings];
10) Set PLC IP in [Device IP] settings;
PLC IP Address: PLC IP
PLC pot No.: 102(fixed)
Network: TCP_Client_2N (fixed)
Wait timeout: depend on actual network situation (more than 1500 ms)
Communication cable
Last updated