11.16 Omron EC55

Supported device: E5CC temperature instrument

HMI settings

Items

Settings

Note

Protocol

Omron EC55

Connection

RS485 (9600, 2, 7, EVEN)

Port No.

None

PLC station No.

0

Address list

Type

Register

Device range

HMI range

Function

Double word

C0

0-13 (Hex)

0-19

Set read only parameter for area 0

C1

0-4D(Hex)

0-77

Set Read/Write parameter for area 0

C3

0-CD(Hex)

0-205

Set Read/Write parameter for area 1

Word

80

0-13(Hex)

0-19

Set read only parameter in area 0

81

0-4D(Hex)

0-77

Set Read/Write parameter in area 0

83

0-CD(Hex)

0-205

Set Read/Write parameter in area 1

CP

-

0-6

Read controller intrinsic property

CS

-

0-2

Read controller states

CA

-

0-17

Action command

Device settings

1) Omron E5CC PLC configuration

After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.

2) According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows

Note:

The communication settings for HMI should be consistent with this setting.

Cable wiring

Note:

1) COM3 is available in PI8000 series and advanced series

2) CA address could not support continuous writing function;

3) Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid

4) When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.

5) When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.

6) Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.

7) When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.

8) Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.

9) Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.

Last updated